Call for Price

In Stock

Analogue Addressable Smoke & Heat detector

Country of Origin: GERMANY

Compare

Features:

  • Highly reliable and accurate thanks to Intelligent

Signal Processing (ISP)

  • Earliest detection of lightest smoke with dual optical

Versions (Dual-Ray technology)

  • Monitors environment for electromagnetic influence

For fast root-cause analysis

  • Automatic and manual addressing

 

Technical specifications

 

Electrical

 

Operating voltage 15 V DC to 33 V DC  
     
Current consumption < 0.55 mA  
     
Alarm output Per data word by two-wire  
      signal line
     
Indicator output Open collector connects 0 V  
      over 1.5 kΩ through, max.
      15 mA
     
Mechanics    
     
Dimensions    
       
Without base   Ø 99.5 x 52 mm
       
With base   Ø 120 x 63.5 mm
     
Housing    
       
Material   Plastic, ABS (Novodur)
       
Color   White, similar to RAL 9010,
      matt finish
       
Weight     Without / With packaging
       
FAP-425-DOTC-R   Approx. 85 g / Approx. 130 g
       
•  FAP-425-DO-R, Approx. 80 g / Approx. 120 g  
  FAP-425-DOT-R    
     
•  FAP-425-O-R, Approx. 80 g / Approx. 120 g  
  FAP-425-OT-R,    
  FAH-425-T-R    
       
FAP-425-O, FAP-425-OT Approx. 75 g / Approx. 115 g  
     
Environmental conditions    
     
Permissible operating temperature    
     
•  FAP-425-DOTC-R -10°C to +50°C  
     
•  FAP-425-DOT-R, -20°C to +50°C  
  FAP-425-OT-R,    
  FAH-425-T-R,    
  FAP-425-OT    
     
•  FAP-425-DO-R, -20°C to +65°C  
  FAP-425-O-R,    
  FAP-425-O    
     
Permissible storage temperature    
     
•  FAP-425-DOTC-R -20°C to +50 °C  
     
•  All versions (except for -25°C to +80°C  
  FAP-425-DOTC-R)    
     
Permissible relative humidity 95% (non-condensing)  
     
Permissible air speed 20 m/s.  
     
Degree of protection (IEC 60529) IP41 ,  
    IP43 with detector base and  
    FAA-420-SEAL or MSC 420  
     
Further characteristics    
     
Response sensitivity    
       
Optical part In accordance with EN 54-7  
    (programmable)  
       
Thermal maximum part > 54°C / > 69°C  
       
Thermal differential part: A2S / A2R / A1 / A1R / BS /  
FAH-425-T-R BR, in line with EN 54‑5  
    (programmable)  
       
Thermal differential part: A2S / A2R / BS / BR, in line  
•  FAP-425-DOTC-R, with EN 54-5 (programmable)  
  FAP-425-DOT-R,    
  FAP-425-OT-R,    
  FAP-425-OT    
       
Gas sensor In ppm range  
     
Individual display LED red and green  
     
Color code    
     
•  FAP-425-O-R, No marking  
  FAP-425-O    
       

 

Reviews