Call for Price

In Stock

2 ZONES CONVENTIONAL CONTROL PANEL

Browse Wishlist
Compare

Descriptions:

The P-C202A/204A conventional fire control panels provide two/four zones of fire detection. All panels have been designed to offer high standards of performance, reliability and quantity and comply fully with BS5839, Part 4, 1988 and EN 54 parts 2 and 4. (Each zone can be connected with 15 conventional fire detectors and infinite no of MCB when using Active EOL).

  • Microprocessor controlled SMT Electronics
  • Compliant with EN54 part 2&4, & BS5839, Part 4, 1988
  • Both end of line resistors and active end of line can be used.
  • Programmable sounder circuits outputs
  • Zone Isolate control
  • Fully monitored sounder circuits
  • Key control evacuate over-ride
  • Class change terminals for remote control
  • Up to 15 fire detectors and infinite manuals call points each zone.

 

SPECIFICATION

PART NUMBER P-C202A P-C204A
OPERATING VOLTAGE 220VAC ± 15%, 50Hz
STANDARD BS5839, Part 4, 1988 and EN 54 parts 2 and 4
APPROVAL CE, LPCB
OPERATING TEMPERATURE -10°C to 40°C @95% relative humidity
NUMBER OF ZONES Two Zone Four Zone
ZONE CAPACITY 15 detectors (AOL); 25 detectors (EOLR)
STANDBY BATTERIES 5 AH, 24hours monitoring state
OUTPUT VOLTAGE 20VDC to 28VDC
STATIC LOADING CURRENT 2.5 mA (when connected with 15 conventional detector)
FIRE ALARMING RESISTANCE 150Ω-1.5kΩ (normal 470Ω)
END OF LINE RESISTOR 4.7kΩ or AEOL (Active End Of Line)
NO. OF SOUNDER OUTPUT 2
SOUNDER OUTPUT CURRENT 1 Ampere (500mA per output)
SOUNDER OUTPUT VOLTAGE 20VDC to 28 VDC
AUX. POWER OUTPUT 20VDC to 28VDC
APPLICATION Indoor Use
MATERIALS AND COLOUR Coated Metal / Grey
DIMENSION 380mm x 95mm x 320mm

 

Reviews

There are no reviews yet.

Be the first to review “SHIELD P-C202A”

Your email address will not be published. Required fields are marked *

Your custom content goes here. You can add the content for individual product
Back to Top